Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The three-phase oil immersed distribution transformer produced by our company adopts a new insulation structure, which improves the ability to withstand short circuit. The core is made of high quality cold-rolled silicon-steel sheet. High quality oxygen free copper wire is used in the high voltage winding as the material and it adopts multilayered drum type structure. All fasteners have been processed with special treatment to prevent them from loosening.
As high-tech product that promoted by the country, the product has many advantages such as high efficiency, low loss.Its social benefits are remarkable that it will save much of electricity consumption and operating cost.
S9 series products reduce the no-load loss,load loss, no-load current, compared with the S7 series decreased by10%, 24%,46%.respectively. thus reducing operating costs by 19%.
S11 series products on the basis of S9 series. the no-load loss is reduced by an average of 30%; the no-load current drops by 70-85% compared to S9; the average temperature rise is reduced by10K, the service life of the product has more than doubled. Even under 20% overloads, it can still run for a long time and thenoise of the product is reduced by 2-4 decibels.
The 'M' in S11(M)R- indicates that the tank is fully sealed, and the fully enclosed distribution transformer eliminates the oil tank in the case of a conventional oil immersed transformer.
The wave fins of the tank instead of the tubing are cold. But the radiating elements, made of high quality cold-rolled sheet comugated tank in a special production line. wave fin with transformer oil volume expansion and shrinkage, so that the transformer is separated from the atmosphere to prevent and slow down oil deterioration and insulation damp. All these ensure the reliability of operation and without maintenance.
The surface of corrugated oil tank is coated with three-proof paint after degreasing, rust removing and phosphating treatment. It is suitable for use in metallurgy, petrochemical industry, mining and other environments.
S11(M) R- R stands for ribbon-wound core. It applies low-loss cold-steel plate of high-quality. It has high degree of mechanization and it is not necessary to shear and punch which eliminate horizontal and longitudinal power connetion of traditional iron core.
1.To obtain lower no-load current, so that the transformer reactive power loss level is lower.
2.To achieve lower noise levels, so that transformers more environmentally friendly.
3.The integral core clamping device is mainly clamping coil, thus further strengthening the coil's ability to withstand short circuit current.
Our company in the traditional structure and mature technology based on a lot of improvements, such as the use of:
1.With longitudinal oil path spiral coil, interior cooling effect better;
2.Improved the effectual support of the loop's terminal face to strengthen the anti-short circuit electricity capability;
3.The new hoisting structure and body positioning structure are adopted to ensure more reliable in long distance transportation and operation;
4.We have many unique and reliable structures to serve you;
5.When you choose higher performance level transformers, you will enjoy greater technique intensity.
1.We Choose oxygen free copper wires with lower resistivity, which will become smoother and burr-free after series of additional surface treatment, so the load loss of our transformer is lower and the electric performance is better.
2.We use high quality silicon steel sheet,with the improvement of performance level, use lower unit loss of silicon steel sheet , so that the transformer no-load loss is lower.
3.We use high-quality laminate insulation, no cracking, even under the effect of short circuit current. wensibudong.
4.We use deep filtered transformer oil, lower water content, gas content, impurity levels, transformer work more reliable.
5.We use high quality rubber sealing materia, which can prevent the transformers from aging or leakage.
6.All raw materials through the quality inspection, and all the raw materials factories has pass through the national standard ISO9000 inspection.
GB 1094.1-1996 |
GB 1094.2-1996 |
JB/T 10088-2004 |
GB 1094.3-2003 |
GB 1094.5-2003 |
GB/T 10237-1988 |
GB/T 6451-1999 |
GB/T 7595-1987 |
JB/T3837-1998 |
XX X - X - X / X X
1 2 3 4 5 6
1.Product model letters ( D-, single phase, S- three-phase, F- air-cooled, Z- on load voltage regulation) |
2.Performance level codes (9, 10, 11, 12) |
3.Special or special construction code (M-,hermetically sealed, R- coil core) |
4.Rated capacity kVA |
5.Voltage level kV |
6.Special use environment code(GY-plateau,WF-corrosion protection, TA- dry tropical, TH warm tropical) |
S11,SZ11 Series 10kv power transformer |
(30kva-2500kva 3-phase duplex winding non-excited tap-changing distribution transformer) |
Rated Capacity (kVA) |
Voltage Combination and Tap range |
Vector Group Symbol |
Loss(kW) |
No- load Current (%) |
Impedance Voltage (%) |
Weight(kg) | Boundary Dimension(mm) (L)x(W)x(H) |
Gauge Vertical/ Horizontal(mm) |
||||||
HV (kV) |
HVTap Range |
LV (kV) |
No- load |
Load | Body | Oi | Total | Fully Sealed | Un-Fully Sealed | |||||
30 | 6 6.3 10 10.5 11 |
±5 ±2X2.5 |
0.4 | Dyn11 Yzn11 Yyn0 |
0.10 | 0.63/0.60 | 2.3 | 4.0 | 150 | 750 | 340 | 730x780x930 | 950x720x1000 | 400/400 |
50 | 0.13 | 0.91/0.87 | 2.0 | 220 | 950 | 440 | 800x750x965 | 1020x700x1035 | 400/400 | |||||
63 | 0.15 | 1.09/1.04 | 1.9 | 260 | 110 | 490 | 820x780x970 | 1140x740x1040 | 400/400 | |||||
80 | 0.18 | 1.31/1.25 | 1.9 | 300 | 120 | 580 | 840x800x1000 | 1060x720x1070 | 400/400 | |||||
100 | 0.20 | 1.58/1.50 | 1.8 | 350 | 120 | 660 | 850x840x1010 | 1105x760x1110 | 450/400 | |||||
125 | 0.24 | 1.89/1.80 | 1.7 | 400 | 130 | 700 | 860x900x1080 | 1120x800x1150 | 550/550 | |||||
160 | 0.28 | 2.31/2.20 | 1.6 | 480 | 160 | 840 | 1220x840x1100 | 1440x760x1290 | 550/550 | |||||
200 | 0.34 | 2.73/2.60 | 1.5 | 560 | 170 | 920 | 1250x860x1150 | 1470x780x1350 | 550/550 | |||||
250 | 0.40 | 3.20/3.05 | 1.4 | 640 | 180 | 1040 | 1260x850x1220 | 1480x780x1420 | 550/550 | |||||
315 | 0.48 | 3.83/365 | 1.4 | 800 | 200 | 1220 | 1340x900x1200 | 1560x840x1400 | 550/550 | |||||
400 | 0.57 | 4.52/4.30 | 1.3 | 980 | 240 | 1460 | 1380x900x1260 | 1600x840x1520 | 550/550 | |||||
500 | 0.68 | 5.41/5.15 | 1.2 | 1130 | 280 | 1710 | 1520x1000x1330 | 1740x960x1590 | 660/660 | |||||
630 | Dyn11 Yyn0 |
0.81 | 6.20 | 1.1 | 4.5 | 1350 | 330 | 2050 | 1580x1040x1270 | 1900x1040x1600 | 660/660 | |||
800 | 0.98 | 7.50 | 1.0 | 1610 | 400 | 2460 | 1650x1160x1400 | 1970x1160x1730 | 820/820 | |||||
1000 | 1.15 | 10.30 | 1.0 | 1690 | 450 | 3680 | 1750x1240x1460 | 2070x1240x1970 | 820/820 | |||||
1250 | 1.36 | 12.00 | 0.9 | 1910 | 500 | 3050 | 1800x1240x1550 | 2100x1240x1870 | 820/820 | |||||
1600 | 1.64 | 14.50 | 0.8 | 2330 | 590 | 3800 | 1830x1800x1930 | 1830x1800x1930 | 820/820 | |||||
2000 | 1.96 | 17.80 | 0.6 | 2750 | 780 | 4660 | 1950x1900x2080 | 1950x1900x2080 | 820/820 | |||||
2500 | 2.31 | 20.70 | 0.5 | 3350 | 920 | 5440 | 2060x1930x2130 | 2160x1930x2130 | 1070/1070 |
S11,SZ11 Series 10kv power transformer |
630kva-6300kva 3-phase Duplex Winding Non-excited Tap-changing Power Transformer |
Rated Capacity (kVA) |
Voltage Combination and Tap range |
Vector Group Symbol |
Loss(kW) |
No- load Current (%) |
Impedance Voltage (%) |
Weight(kg) | Gauge Vertical/ Horizontal(mm) |
|||||
HV (kV) |
HVTap Range |
LV (kV) |
No- load |
Load | Body | Oi | Total | |||||
630 | 6 6.3 10 10.5 11 |
±5 ±2X2.5 |
3 3.15 6.3 |
Yd11 | 0.84 | 6.93 | 1.1 | 5.5 | 1780 | 450 | 2710 | 750/660 |
800 | 1.02 | 8.46 | 1.0 | 2100 | 520 | 3310 | 850/660 | |||||
1000 | 1.20 | 9.92 | 1.0 | 2580 | 600 | 3860 | 850/820 | |||||
1250 | 1.42 | 11.80 | 0.9 | 2880 | 700 | 4370 | 850/820 | |||||
1600 | 1.71 | 14.11 | 0.8 | 3400 | 780 | 4760 | 900/820 | |||||
2000 | 2.04 | 16.93 | 0.8 | 3800 | 890 | 5570 | 900/820 | |||||
2500 | 2.40 | 19.67 | 0.8 | 4350 | 960 | 6670 | 1070/1070 | |||||
3150 | 2.84 | 23.09 | 0.7 | 4940 | 1180 | 8500 | 1070/1070 | |||||
4000 | 10 10.5 11 |
3.15 6.3 |
3.48 | 27.36 | 0.7 | 5900 | 1580 | 9850 | 1070/1070 | |||
5000 | 4.16 | 31.38 | 0.7 | 6850 | 1760 | 11580 | 1070/1070 | |||||
6300 | 4.96 | 35.06 | 0.6 | 7920 | 1910 | 13650 | 1070/1070 |
200kva~2500kva 3-phase duplex winding on-load tap-changing distribution transformer |
Rated Capacity (kVA) |
Voltage Combination and Tap range |
Vector Group Symbol |
Loss(kW) |
No- load Current (%) |
Impedance Voltage (%) |
Weight(kg) | Gauge Vertical/ Horizontal(mm) |
|||||
HV (kV) |
HVTap Range |
LV (kV) |
No- load |
Load | Body | Oi | Total | |||||
200 | 6 6.3 10 |
±4×2.5 | 0.4 | Dyn11 Yyn0 |
0.39 | 2.91 | 1.5 | 4.0 | 980 | 260 | 1530 | 650/550 |
250 | 0.45 | 3.42 | 1.4 | 1070 | 310 | 1740 | 650/550 | |||||
315 | 0.54 | 4.10 | 1.4 | 1320 | 350 | 1980 | 650/550 | |||||
400 | 0.65 | 4.96 | 1.3 | 1580 | 430 | 2270 | 750/550 | |||||
500 | 0.77 | 5.90 | 1.2 | 1750 | 450 | 2500 | 750/660 | |||||
630 | 0.97 | 7.27 | 1.1 | 4.5 | 1900 | 530 | 2920 | 750/660 | ||||
800 | 1.13 | 8.89 | 1.0 | 2150 | 600 | 3320 | 850/660 | |||||
1000 | 1.38 | 10.43 | 1.0 | 2480 | 680 | 3710 | 850/820 | |||||
1250 | 1.58 | 12.40 | 0.9 | 2620 | 770 | 4200 | 850/520 | |||||
1600 | 1.94 | 14.79 | 0.8 | 3100 | 880 | 4850 | 900/820 | |||||
2000 | 2.27 | 18.69 | 0.6 | 3980 | 1080 | 5880 | 900/820 | |||||
2500 | 2.52 | 21.74 | 0.6 | 3950 | 1300 | 6370 | 1070/1070 |
S11 Series 20kv distribution transformer |
30kva~2500kva 3-phase duplex winding non-excited tap-changing distribution transformer |
Rated Capacity (kVA) | Voltage Combination and Tap range | Vector Group Symbo | No-load Loss(kW) | Load Loss(kW) | No-load current(%) | Short-circult Impedance Voitage(%) | ||
HV(kV) | HVTap Range | LV(KV) | ||||||
30 | 20 | ±5 | 0.4 | Dyn11 Yzn11 Yyn0 |
0.10 | 0.69/0.66 | 2.1 | 5.5 |
50 | 0.13 | 1.01/0.96 | 2.0 | |||||
63 | 0.15 | 1.20/1.15 | 1.9 | |||||
80 | 0.18 | 1.44/1.37 | 1.8 | |||||
100 | 0.20 | 1.73/1.65 | 1.6 | |||||
125 | 0.24 | 2.08/1.98 | 1.5 | |||||
160 | 0.29 | 2.54/2.42 | 1.4 | |||||
200 | 0.34 | 3.00/2.86 | 1.3 | |||||
250 | 0.40 | 3.52/3.35 | 1.2 | |||||
315 | 0.48 | 4.21/4.01 | 1.1 | |||||
400 | 0.57 | 4.97/4.73 | 1.0 | |||||
500 | 0.68 | 5.94/5.66 | 1.0 | |||||
630 | 0.81 | 6.82 | 0.9 | 6.0 | ||||
800 | 0.98 | 8.25 | 0.8 | |||||
1000 | 1.15 | 11.33 | 0.7 | |||||
1250 | 1.38 | 13.20 | 0.7 | |||||
1600 | 1.66 | 15.95 | 0.6 | |||||
2000 | 1.95 | 19.14 | 0.6 | |||||
2500 | 2.34 | 22.22 | 0.5 |
S13 Series 10kv distribution transformer |
30kva~2500kva 3-phase duplex winding non-excited tap-changing distribution transformer |
Rated Capacity(kVA) | Voltage Combination and Tap range | Vector Group Symbol |
Loss (kW) |
No- load current (%) |
Impedance Voltage (%) |
Weight(kg) | BoundaryDimension(mm) (L)x(W)x(H) |
Gauge vertical/horizonta (mm) |
||||||
HV (kV) |
HVTap Range(%) |
LV (kV) |
No-load | Load | Body | Oi | Total | Fully sealed | Un-Fully sealed | |||||
30 | 6 6.3 10 10.5 11 |
±5 ±2X2.5 |
0.4 | Dyn11 Yzn11 Yyn0 |
0.08 | 0.63/0.60 | 2.3 | 4.0 | 130 | 700 | 300 | 710x710x930 | 930x580x1000 | 400/400 |
50 | 0.10 | 0.91/0.87 | 2.0 | 200 | 800 | 400 | 730x710x1010 | 950x600x1080 | 400/400 | |||||
63 | 0.11 | 1.09/1.04 | 1.9 | 240 | 900 | 450 | 750x730x1040 | 970x630x1100 | 400/400 | |||||
80 | 0.13 | 1.31/1.25 | 1.9 | 280 | 100 | 520 | 760x740x1060 | 980x640x1120 | 400/400 | |||||
100 | 0.15 | 1.58/1.50 | 1.8 | 310 | 100 | 550 | 770x750x1130 | 1000x650x1200 | 450/400 | |||||
125 | 0.17 | 1.89/1.80 | 1.7 | 370 | 120 | 640 | 800x770x1150 | 1030x670x1220 | 550/550 | |||||
160 | 0.20 | 2.31/2.20 | 1.6 | 440 | 130 | 740 | 820x780x1240 | 1050x680x1310 | 550/550 | |||||
200 | 0.24 | 2.73/2.60 | 1.5 | 500 | 140 | 810 | 840x810x1260 | 1070x700x1330 | 550/550 | |||||
250 | 0.29 | 3.20/3.05 | 1.4 | 610 | 160 | 970 | 870x850x1300 | 1100x750x1370 | 550/550 | |||||
315 | 0.34 | 3.83/365 | 1.4 | 750 | 200 | 1200 | 1180x820x1390 | 1400x720x1460 | 550/550 | |||||
400 | 0.41 | 4.52/4.30 | 1.3 | 900 | 240 | 1420 | 1260x840x1450 | 1480x760x1520 | 550/550 | |||||
500 | 0.48 | 5.41/5.15 | 1.2 | 1050 | 250 | 1620 | 1300x860x1500 | 1560x800x1600 | 660/660 | |||||
630 | Dyn11 Yyn0 |
0.57 | 6.20 | 1.1 | 4.5 | 1240 | 280 | 1860 | 1370x890x1470 | 1630x930x1680 | 660/660 | |||
800 | 0.70 | 7.50 | 1.0 | 1510 | 340 | 2250 | 1430x930x1580 | 1960x930x1680 | 820/820 | |||||
1000 | 0.83 | 10.30 | 1.0 | 1560 | 360 | 2410 | 1600x1100x1610 | 1860x1100x1720 | 820/820 | |||||
1250 | 0.97 | 12.00 | 0.9 | 1.91 | 420 | 2930 | 1690x1140x1750 | 1950x1140x1860 | 820/820 | |||||
1600 | 1.17 | 14.50 | 0.8 | 2320 | 520 | 3630 | 1820x1650x2060 | 1820x1650x2060 | 820/820 | |||||
2000 | 1.26 | 17.80 | 0.6 | 2820 | 660 | 4550 | 1920x1750x2160 | 1920x1750x2160 | 820/820 | |||||
2500 | 1.49 | 20.70 | 0.5 | 3550 | 760 | 5470 | 2020x1910x2260 | 2020x1910x2260 | 1070/1070 |
S13 Series 20kv distribution transformer |
30kva~2500kva 3-phase duplex winding non-excited tap-changing distribution transformer |
Rated Capacity (kVA) |
VoltageCombination and Tap range |
Vector Group Symbo | No-load Loss(kW) | Load Loss(kW) | No-load curent(%) | Short-circult Impedance Voltage(%) | ||
HV (kV) |
HVTap Range(%) |
LV (kV) |
||||||
30 | 20 | ±5 | 0.4 | Dyn11 Yzn11 Yyn0 |
0.08 | 0.66/0.63 | 2.1 | 5.5 |
50 | 0.10 | 0.96/0.91 | 2.0 | |||||
63 | 0.11 | 1.14/1.09 | 1.9 | |||||
80 | 0.13 | 1.38/1.31 | 1.8 | |||||
100 | 0.15 | 1.66/1.58 | 1.6 | |||||
125 | 0.17 | 1.98/1.89 | 1.5 | |||||
160 | 0.20 | 2.43/2.31 | 1.4 | |||||
200 | 0.24 | 2.87/2.73 | 1.3 | |||||
250 | 0.29 | 3.36/3.20 | 1.2 | |||||
315 | 0.34 | 4.02/3.83 | 1.1 | |||||
400 | 0.41 | 4.77/4.51 | 1.0 | |||||
500 | 0.48 | 5.68/5.40 | 1.0 | |||||
630 | 0.57 | 6.51 | 0.9 | 6.0 | ||||
800 | 0.70 | 7.88 | 0.8 | |||||
1000 | 0.83 | 10.81 | 0.7 | |||||
1250 | 0.97 | 12.60 | 0.7 | |||||
1600 | 1.17 | 15.22 | 0.6 | |||||
2000 | 1.26 | 19.74 | 0.6 | |||||
2500 | 1.49 | 21.73 | 0.5 |
*The above table data does not represent the parameter configuration of all models, please contact us for more information. |
Wenzhou Naisite Electric Co., Ltd is a technology oriented transmission and distribution equipment manufacturing enterprises, since its establishment in 2011, focus on transmission and distribution equipment technology progress, advocating technological innovation, introduce new energy prefabricated, a secondary fusion ring cage, environmental protection cabinet,Transformers, cable branch box, box type substation such as intelligent high and low voltage transmission and distribution equipment. Applicable to electric power, railway, petrochemical, subway, municipal construction, steel, coal and other industries. The company's products have achieved a number of technological breakthroughs in environmental protection, miniaturization, intelligence, maintenance free and other aspects. The headquarters of Wenzhou Naisi Electric Co., Ltd is located in the core area of Wenzhou Yueqing Economic Development Zone, "the capital of Electrical appliances in China". Has an excellent domestic intelligent distribution network products assembly line.
The company has a vacuum box helium leak detection system, local discharge test laboratory and other advanced inspection and test equipment system. With the basic experimental facilities and research environment needed for advanced technology development and scientific research, the products are tested according to the international IEC standards. The enterprise has passed the IS09001 quality system certification, IS014001 environmental system certification and OHSAS18001 occupational health and safety management system certification, the products have been obtained the CNAS national accreditation laboratory certification report.
Q: Are you a trading company or manufacturer ? |
A: We are a professional factory with 10 years experience in the field of High and Low voltage switchgears,Substation,transformers,cable distribution box and various electrical equipment, such as vacuum circuit breaker , load break switch etc.Our factory is the excellent supplier of State Grid Corporation of China . |
Q: Do you accept customized serveice ? |
A: We offer OEM/ODM service , can print your logo on product . our professional technical and quotation team can provice a satisfied project according to your drawing and parameters . |
Q: What is your MOQ? |
A: Our MOQ is 1 piece . |
Q:How long is your delivery lead time ? |
A: It depends on your product requirement and quantity . Generally , 5~10 working days is available . |
Q: How do you solve quality problems? |
A: Please porvide detailed photoes of quality problems. our technical and quality testing department will analyse.we will make a satisfied soluton within 2 days. |
Q: What is your payment terms ? |
A: 30%T/T in advance,70% before shipment . West union , L/C are also acceptable . |